Description
INPUT DATA
Number of MPP trackers 2
Max. input current (Idc max)
27,0 / 16,5 A
Max. short circuit current, module array*
55,7 / 34,0 A
DC input voltage range (Udc min – Udc max)
200 – 1000 V
Feed-in start voltage (Udc start)
200 V
Nominal input voltage (Udc,r)
600 V
MPP voltage range (Umpp min – Umpp max)
270 – 800 V
Usable MPP voltage range 200 – 800 V
Number of DC connections 3 + 3
Max. PV generator power (Pdc max)
15 kWpeak
OUTPUT DATA
AC nominal output (Pac,r)
10 kW
Max. output power (Pac max)
10 kVA
AC output current (Iac nom)
14,4 A
Grid connection (Uac,r)
3~ NPE 400/230, 3~ NPE 380/220 V
AC voltage range (Umin – Umax)
150 – 280 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin – fmax)
45 – 65 Hz
Total harmonic distortion <3% @Pnom (230/400VAC 50Hz)
Power factor (cos φac,r)
0 – 1 ind,/cap,
GENERAL DATA
Width
510 mm
Height
725 mm
Depth
225 mm
Weight 32,1 kg
Weight incl. packaging 38,5 kg
Degree of protection IP 66
Protection class 1
Overvoltage category (DC / AC) 1)
2 / 3
Night-time consumption < 1 W Cooling Regulated air cooling Installation Indoor and outdoor installation Ambient temperature range -25°C – +60°C Permitted humidity 0 – 100 % Max. altitude 2) 2,000 m / 3,400 m DC connection technology 6x DC+ and 6x DC- screw terminals 2.5 – 16 mm² AC connection technology 5-pin AC screw terminals 2.5 – 16 mm² Certificates and compliance with standards IEC 62109-1/-2, IEC 62116, IEC 61727, VDE 0126-1-1/A1, VDE AR-N 4105, G98/1, G99/1, AS/NZS 4777.2, UNE 206007-1, CEI 0-21, CEI 0-16, NRS 097-2-1, TOR Erzeuger Typ A, EN 50549-1/-2, IEC 61683, IEC60068, IEC 63027:2023 Interference emission class B EFFICIENCY Max. efficiency (PV – grid) 97,8 % European efficiency (ηEU) 95,5 / 97,1 / 96,3% η at 5% Pac,r 3) 89,0 / 91,5 / 87,1% η at 10% Pac,r 3) 92,6 / 94,8 / 92,6% η at 20% Pac,r 3) 94,8 / 96,7 / 95,5% η at 25% Pac,r 3) 95,3 / 97,0 / 96,1% η at 30% Pac,r 3) 95,7 / 97,3 / 96,5% η at 50% Pac,r 3) 96,2 / 97,6 / 97,1% η at 75% Pac,r 3) 96,2 / 97,8 / 97,4% η at 100% Pac,r 3) 96,2 / 97,8 / 97,5% MPP adaptation efficiency >99,9%
PROTECTION DEVICES
DC insulation measurement Yes
Overload behaviour Operating point shift. Power limitation
DC disconnector Yes
DC Reverse polarity protection Yes
Arc fault circuit interrupter (Fronius Arc Guard) Yes
INTERFACES
WLAN / Ethernet LAN Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital inputs/outputs Interface to ripple control receiver, energy management
USB (type A socket) 4)
Data logging, inverter update via USB flash drive
2x RS422 (RJ45 socket) 4)
Fronius Solar Net
Signalling output 4)
Energy management (floating relay output)
Datalogger and web server Included
External input 4)
S0 meter connection / Evaluation of overvoltage protection
RS485 Modbus RTU SunSpec or meter connection
Reviews