HomeShopTesting EquipmentFluke 1623-2 GEO Earth Ground Tester

Description

Fluke 1623-2 GEO Earth Ground Tester

The Fluke 1623-2 GEO Earth Ground Tester offers expanded versatility and ease of set up. This all leads to a more effective and efficient earth ground tester that allows you to work faster and in more locations.

The Fluke 1623-2 is a unique earth ground tester that can perform all four types of earth ground measurement:

3- and 4-Pole Fall of Potential (using stakes)
4-Pole Soil Resistivity testing (using stakes)
Selective testing (using 1 clamp and stakes)
Stakeless testing (using 2 clamps only)

Easy to use, for each test the testers inform you which stakes or clamps need to be connected and the large rotary switch can be used even with a gloved hand.

Stakeless Testing:

The 1623-2 is able to measure earth ground loop resistance using only clamps. With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by the clamp and the current is measured using the second clamp. The 1623-2 then automatically determines the resistance of the earth ground rod.

With stakeless testing, the earth ground rod does not need to be disconnected – leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system – a major time saver. You can also perform earth ground tests in places you’ve not considered before: inside buildings, power pylons or anywhere you don’t have access to soil.

Included with the 1623-2:

1623-2 Tester
2 Test leads
Batteries
User Manual
Quick Reference Guide
USB CableFluke 1623-2 GEO Earth Ground Tester

The Fluke 1623-2 GEO Earth Ground Tester offers expanded versatility and ease of set up. This all leads to a more effective and efficient earth ground tester that allows you to work faster and in more locations.

The Fluke 1623-2 is a unique earth ground tester that can perform all four types of earth ground measurement:

3- and 4-Pole Fall of Potential (using stakes)
4-Pole Soil Resistivity testing (using stakes)
Selective testing (using 1 clamp and stakes)
Stakeless testing (using 2 clamps only)

Easy to use, for each test the testers inform you which stakes or clamps need to be connected and the large rotary switch can be used even with a gloved hand.

Stakeless Testing:

The 1623-2 is able to measure earth ground loop resistance using only clamps. With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by the clamp and the current is measured using the second clamp. The 1623-2 then automatically determines the resistance of the earth ground rod.

With stakeless testing, the earth ground rod does not need to be disconnected – leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system – a major time saver. You can also perform earth ground tests in places you’ve not considered before: inside buildings, power pylons or anywhere you don’t have access to soil.

Included with the 1623-2:

1623-2 Tester
2 Test leads
Batteries
User Manual
Quick Reference Guide
USB Cable

Specifications

Detailed Specifications

General

Display: 1999 digit LCD
Display with special symbols, digit height 25 mm, fluorescent backlight

User interface
Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button

Robust, water and dust resistant
Instrument is designed for tough environmental conditions (rubber protective cover, IP56)

Memory
Internal memory storage up to 1500 records accessible via USB port

Temperature Range

Operating temperature
-10 °C to 50 °C (14 °F to 122 °F)

Storage temperature
-30 °C to 60 °C (-22 °F to 140 °F)

Temperature coefficient
± 0.1 % of reading/°C <18 °C >28 °C

Intrinsic error
Refers to the reference temperature range and is guaranteed for 1 year

Operating error
Refers to the operating temperature range and is guaranteed for 1 year

Climatic class
C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH

Protective type
IP56 for case, IP40 for battery door according to EN60529

Safety
Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree 2

EMC (emission immunity)
IEC61326-1: Portable

Quality system
Developed, designed and manufactured according to DIN ISO 9001

External voltage
V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values V ext rejection > 120 dB (162⁄3, 50, 60, 400 Hz)

Measuring time
Typical 6 seconds

Max. overload
250 V rms (pertains to misuse)

Auxiliary power
6 x 1.5 V Alkaline (type AA LR6)

Battery life span
Typical > 3,000 measurements

Dimensions (WxHxD)
250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in)

Weight
1.1 kg (2.43 lb) including batteries
7.6 kg (16.8 lb) incl. accessories and batteries in carrying case

RA 3-Pole Ground Resistance Measurement (IEC 1557-5)

Switch position
RA 3-pole

Resolution
0.001 Ω to 10 Ω

Measuring range
0.020 Ω to 19.99 kΩ

Accuracy
± (2 % rdg + 3 d)

Operating error
± (5 % rdg + 3 d)

Measuring Principle: Current/Voltage Measurement

Measuring voltage
Vm = 48 V ac

Short-circuit current
> 50 mA

Measure frequency
128 Hz

Probe resistance (RS)
Max 100 kΩ

Auxiliary earth electrode resistance (RH)
Max 100 kΩ

Additional error from RH and RS
RH[kΩ]RS[kΩ]/RA[Ω]0.2 %

Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.

RA 4-Pole Ground Resistance Measurement (IEC 1557-5)

Switch position
RA 4-pole

Resolution
0.001 Ω to 10 Ω

Measuring range
0.020 Ω to 19.99 kΩ

Accuracy
± (2 % rdg + 3 d)

Operating error
± (5 % rdg + 3 d)

Measuring Principle: Current/Voltage Measurement

Measuring voltage
Vm = 48 V ac

Short-circuit current
> 50 mA

Measure frequency
128 Hz

Probe resistance (RS + RES)
Max 100 kΩ

Auxiliary earth electrode resistance (RH)
Max 100 kΩ

Additional error from RH and RS
RH[kΩ]RS[kΩ]/RA[Ω]0.2 %

Monitoring of RS and RH with error indicator.
Automatic range selection.

RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )

Switch position
RA 3-pole with clamp

Resolution
0.001 Ω to 10 Ω

Measuring range
0.020 Ω to 19.99 kΩ

Accuracy
± (7 % rdg + 3 d)

Operating error
± (10 % rdg + 5 d)

Measuring Principle: Current/Voltage Measurement (with External Current Clamp)

Measuring voltage
Vm = 48 V ac

Short-circuit current
> 50 mA

Measure frequency
128 Hz

Probe resistance (RS)
Max 100 kΩ

Auxiliary earth electrode resistance (RH)
Max 100 kΩ

Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.

RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )

Switch position
RA 4-pole with clamp

Resolution
0.001 Ω to 10 Ω

Measuring range
0.020 Ω to 19.99 kΩ

Accuracy
± (7 % rdg + 3 d)

Operating error
± (10 % rdg + 5 d)

Measuring Principle: Current/Voltage Measurement (with External Current Clamp)

Measuring voltage
Vm = 48 V ac

Short-circuit current
> 50 mA

Measure frequency
128 Hz

Probe resistance (RS)
Max 100 kΩ

Auxiliary earth electrode resistance (RH)
Max 100 kΩ

Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.

Stakeless Ground Loop Measurement (2 Clamps )

Switch position
RA 4-pole 2 clamps

Resolution
0.001 Ω to 10 Ω

Measuring range
0.020 Ω to 19.99 kΩ

Accuracy
± (7 % rdg + 3 d)

Operating error
± (10 % rdg + 5 d)

Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers

Measuring voltage
Vm = 48 V ac

Measure frequency
128 Hz

Noise current (IEXT)
Max. IEXT = 10 A (ac) (RA < 20 Ω) Max. IEXT = 2 A (ac) (RA > 20 Ω)

Automatic range selection.
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.

Click here for complete specifications on the Fluke 1623-2

What’s included with the Fluke 1623-2
Fluke Tester
Professional Carrying Case
Batteries
USB Cable
Quick Reference Guide